Start-up
Contents of this chapter
This chapter describes the start-up procedure of the converter unit. The information
is valid for cabinet-installed ACS880-1607LC DC/DC converter units.
The default device designations are given in square brackets, for example, [Q11]. The
same device designations are also used in the delivery-specific circuit diagrams.
Refer to the delivery-specific circuit diagrams when you do the start-up tasks.
WARNING!
Only a qualified electrical professional can do the work described in this chapter.
The persons who does the work must know the energy storage system, the
DC/DC converter control program and the operation principle of the DC/DC
converter.
Obey the safety instructions of the drive. If you ignore them, injury or death,
or damage to the equipment can occur. The safety instructions are given in
ACS880 liquid-cooled multidrives cabinets and modules safety instructions
(3AXD50000048633 [English]).
Before you start, connect a control panel to the DC/DC converter unit. ABB recommends
that you also have a PC with a drive commissioning tool (Drive Composer) connected.
For information on the use of the control panel, refer to ACS-AP-I, -S, -W and ACH-AP-H,
-W Assistant control panels user's manual (3AUA0000085685 [English]). For information
on the use of the Drive Composer PC tool, refer to Drive Composer start-up and
maintenance PC tool user's manual (3AUA0000094606 [English]).