If the outer surface of the shield is non-conductive:
Cut the shield at the midpoint of the peeled part. Be careful not to cut the
conductors or the grounding wire.
Turn the conductive side of the shield inside out over the insulation.
Cover the exposed shield and the peeled cable with copper foil to keep the shielding
continuous.
Stripped cableA
1
A B C
2 2
3
4
Conductive surface of the shield exposedB
Stripped part covered with copper foilC
Cable shield1
Copper foil2
Shielded twisted pair3
Grounding wire4
58 Electrical installation