Technical data 111
Nominal ratings with 460 V AC supply
-050A-5 R3 42 50 66 22 46 22 44 22
-061A-5 R4 55 61 78 30 57 30 52 22
-078A-5 R4 65 78 104 37 74 37 66 37
-094A-5 R4 82 94 124 45 90 45 75 37
3AXD10000434191
See symbol definitions on page 112.
Drive type
ACS880-M04
Frame
size
Input
ratings
Output ratings
Nominal No-overload
use
Light-
overload use
Heavy-
duty use
I
1N
*I
1N
I
2N
I
Max
P
N
I
Ld
P
Ld
I
Hd
P
Hd
A A A A hp A hp A hp
-03A0-5 R1 2.3 3.8 3.0 4.4 1.5 2.8 1.0 2.5 1.0
-03A6-5 R1 3.1 5.6 3.6 5.3 2.0 3.4 2.0 3.0 1.5
-04A8-5 R1 4.0 6.8 4.8 7.0 3.0 4.5 2.0 4.0 2.0
-06A0-5 R1 5.5 9.4 6.0 8.8 3.0 5.5 3.0 5.0 3.0
-08A0-5 R1 6.6 11.2 8.0 10.5 5.0 7.6 5.0 6.0 3.0
-010A-5 R2 8.7 13 10.5 13.5 5.0 9.7 5.0 9.0 5.0
-014A-5 R2 12 18 14 16.5 7.5 13.0 7.5 11.0 7.5
-018A-5 R2 1623182110 16.81014.010
-025A-5 R3 20 25 33 15 23 15 19.0 10
-030A-5 R3 26 30 36 20 28 20 24 15
-035A-5 R3 30 35 44 25 32 20 29 20
-044A-5 R3 36 44 53 30 41 30 35 25
-050A-5 R3 42 50 66 30 46 30 44 30
-061A-5 R4 55 61 78 40 57 40 52 40
-078A-5 R4 65 78 104 50 74 50 66 50
-094A-5 R4 82 94 124 60 90 60 75 50
3AXD10000434191
See symbol definitions on page 112.
Drive type
ACS880-M04
Frame
size
Input
ratings
Output ratings
Nominal No-
overload
use
Light-overload
use
Heavy-duty
use
I
1N
*I
1N
I
2N
I
Max
P
N
I
Ld
P
Ld
I
Hd
P
Hd
A A A A kW A kW A kW