16 Safety instructions
Additional instructions and notes
WARNING! Follow these instructions. If you ignore them, injury or death, or
damage to the equipment can occur.
If you install the drive on an IT system (an ungrounded power system or a high-
resistance-grounded [over 30 ohms] power system), disconnect the internal EMC
filter; otherwise the system will be connected to ground potential through the EMC
filter capacitors. This can cause danger or damage the drive. See page 76.
Note: Disconnecting the internal EMC filter increases the conducted emission
and reduces the drive EMC compatibility considerably. See section Compliance
with the European EMC Directive on page 134.
If you install the drive on a corner-grounded TN system, disconnect the internal
EMC filter; otherwise the system will be connected to ground potential through the
EMC filter capacitors. This will damage the drive. See page 159.
Note: Disconnecting the internal EMC filter increases the conducted emission
and reduces the drive EMC compatibility considerably. See section Compliance
with the European EMC Directive on page 134.
Use all ELV (extra low voltage) circuits connected to the drive only within a zone
of equipotential bonding, that is, within a zone where all simultaneously
accessible conductive parts are electrically connected to prevent hazardous
voltages appearing between them. You can accomplish this by a proper factory
grounding, that is, make sure that all simultaneously accessible conductive parts
are grounded to the protective earth (PE) bus of the building.
Do not do insulation or voltage withstand tests on the drive or drive modules.
Note:
The motor cable terminals of the drive are at a dangerous voltage when the input
power is on, regardless of whether the motor is running or not.
The DC and brake resistor terminals (UDC+, UDC-, R+ and R-) are at a
dangerous voltage.
External wiring can supply dangerous voltages to the terminals of relay outputs.
The Safe torque off function does not remove the voltage from the main and
auxiliary circuits. The function is not effective against deliberate sabotage or
misuse.
WARNING! Use a grounding wrist band when you handle the printed circuit
boards. Do not touch the boards unnecessarily. The components on the boards
are sensitive to electrostatic discharge.