122 Technical data
AC input (supply) connection
Voltage (U
1
) 200…240 V AC +/-10%, 3-phase
380…500 V AC +10%/-15%, 3-phase
Network type Grounded (TN, TT) or ungrounded (IT).
Note: If the installation site is higher than 2000 m (6600 ft) above sea level,
connection of the drive to an ungrounded (IT) or corner-grounded delta
network is not allowed.
Short-circuit
withstand
strength
(IEC 60439-1
100 kA when protected by fuses given in the Supply cable fuses on
page 118.
Frames R1 and R2: Thermal dimensioning of the DC capacitors is based
on max. 5 kA short-circuit current. An input choke should be used to
achieve 100 kA.
Short-circuit
current
protection
(UL 61800-5-1,
CSA C22.2 No.
274-13)
US and Canada: The drive is suitable for use on a circuit capable of
delivering not more than 100 kA symmetrical amperes (rms) at 500 V
maximum when protected by fuses given in the Supply cable fuses on
page 118.
Frequency 50…60 Hz
±
5%
Imbalance Max.
±
3% of nominal phase to phase input voltage
Fundamental
power factor
(cos phi
1
)
0.98 (at nominal load)
Terminal s Frame R1: Detachable screw terminal block for 0.25…4 mm
2
wire.
Frame R2: Detachable screw terminal block for 0.5…6 mm
2
wire.
Frames R3 and R4: Screw lugs for 6…70 mm
2
wire included. Suitable
crimp lugs can be used instead.