58 Planning the electrical installation
Typical power cable sizes
The table below gives copper cable types with concentric copper shield for the drives
with nominal current. The value separated by the plus sign means the diameter of the
PE conductor.
Drive type
ACS880-M04
Frame size IEC
1)
US
Cu cable type
mm
2)
AWG/kcmil
-03A0-2/5 R1 3×1.5 + 1.5
16
-03A6-2/5 R1 3×1.5 + 1.5
16
-04A8-2/5 R1 3×1.5 + 1.5
16
-06A0-2/5 R1 3×1.5 + 1.5
16
-08A0-2/5 R1 3×1.5 + 1.5 16
-010A-2/5 R2 3×1.5 + 1.5 16
-014A-2/5 R2 3×2.5 + 2.5 14
-018A-2/5 R2 3×4 + 4
2)
14
-025A-2/5 R3 3×10 + 10 6
-030A-2/5 R3 3×10 + 10 6
-035A-2/5 R3 3×10 + 10 6
-044A-2/5 R3 3×10 +10 6
-050A-2/5 R3 3×10 +10 6
-061A-2/5 R4 3×10 +10 6
-078A-2/5 R4 3×10 +10 6
-094A-2/5 R4 3×10 +10 6
3AXD10000434191.xls
1)
The cable sizing is based on max. 6 cables laid on a cable ladder side by side, ambient temperature 30 °C,
PVC insulation, surface temperature 70 °C .
For other conditions, size of the cables according to local safety regulations, appropriate input voltage and
load current of the drive, see page 110 for the accepted cable sizes of the drive.
2)
Without additional choke
See also Supply cable fuses on page 118.