130 Technical data
Ambient conditions
Environmental limits for the drive are given below. The drive must be used
in a heated, indoor, controlled environment.
Operation
installed for stationary
use
Storage
in the protective
package
Transportation
in the protective
package
Installation site
altitude
Non-corner grounded
TN and TT systems: 0
to 4000 m (13123 ft)
above sea level.
Other systems
: 0 to
2000 m (6561 ft) above
sea level.
Above 1000 m
(3281 ft), see section
Altitude derating on
page 113.
--
Air temperature -10 to +55°C
(14 to 131°F).
No frost
allowed. See section
Derating on page 113.
-40 to +70°C
(-40 to +158°F)
-40 to +70°C
(-40 to +158°F)
Relative
humidity
0 to 95% Max. 95% Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the
presence of corrosive gases.
Contamination
levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
No conductive dust allowed.
According to IEC
60721-3-3:
Chemical gases: Class
3C2
Solid particles: Class
3S2
The drive must be
installed in clean air
according to enclosure
classification. Cooling
air must be clean, free
from corrosive
materials and
electrically conductive
dust.
According to IEC
60721-3-1:
Chemical cases: Class
1C2
Solid particles: Class
1S2
According to IEC
60721-3-2:
Chemical cases: Class
2C2
Solid particles: Class
2S2