EMC filters 165
Installing the JFI-B1 filter
To install the JFI-B1 EMC filter,
1. Remove the UDC+/- and U1/V1/W1 terminal blocks (1), and the upper power
cable clamp plate (2) from the drive.
2. Push the filter into the connectors.
3. Fasten the filter to the drive module base with two screws (3). Tighten to 1.5 N·m
(13 lbf·in).
4. Fasten the top edge of the filter to the mounting base with two screws (4).
5. Fasten the power cable clamp plate at the top of the filter. Tighten to 1.5 N·m
(13 lbf·in).