EasyManua.ls Logo

ABB ACS880-M04 - Mains Chokes; Contents of this Chapter; When Is a Mains Choke Required

ABB ACS880-M04
195 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mains chokes 155
13
Mains chokes
Contents of this chapter
This chapter describes how to select and install mains chokes for the drive module.
The chapter also contains the relevant technical data.
When is a mains choke required?
With frames R1 and R2, the need for an external choke should be determined on a
case-by-case basis. With frames R3 and R4, the drive modules have an internal
mains choke.
The main choke typically
reduces harmonics in the input current
reduces the r.m.s. input current
reduces supply disturbance and low-frequency interference
increases the allowed DC bus continuous power
ensures even current distribution in common DC configurations (see
DC connection on page 82).