Electrical installation 97
6. Strip the cable ends and conductors. When connecting to the drive I/O, also
remove the shield along with the outer sheathing, and use electrical tape or shrink
tubing to contain the strands. Elsewhere, twist the outer shield strands into a
bundle, crimp a lug onto it and connect it to the nearest chassis grounding point.
7. Connect the conductors to appropriate terminals (refer to chapter Control
connections to the ZCU control unit).
8. Refit any shrouds removed earlier.
2
3
4
1
Keep as short as
possible
*If no dedicated “shield”
connector is provided,
ground the inner cable
shields to the chassis.
SHIELD*
Where grounding clamps are
not available, twist the shield
strands into a bundle, crimp a
lug terminal onto it and fasten
the lug to the chassis. Secure
the cable into place with eg.
cable ties.
At the other end of the
cable, leave the shield
unconnected, or connect
it to ground via a
capacitor with a value of
a few nanofarads.