AWT210 | 2-WIRE CONDUCTIVITY, PH/ORP, PION TRANSMITTER | OI/AWT210-EN REV. C
15
6 Electrical installation
DANGER
• If the transmitter is used in a manner not specified by the
Company, the protection provided by the equipment may
be impaired.
• Refer to page 7 for electrical installation
considerations in Hazardous areas.
• The transmitter conforms to Installation Category II of IEC
61010.
• All equipment connected to the transmitter’s terminals
must comply with local safety standards (IEC 60950,
EN61010-1).
DANGER – CONNECTION/CABLE
REQUIREMENTS
• The connection terminals accept cables with peripheral
wire cross-section of:
min.: 0.14 mm
2
(26 AWG)
max.: 1.5 mm
2
(14 AWG)
• Do not use a rigid conductor material as this can result in
wire breaks.
• Ensure the connecting cable is flexible.
• To ensure the sensor cable length is sufficient, allow an
additional 100 mm (4 in) of cable to pass through cable
glands into the housing.
• Ensure the correct connections are made to suit the
transmitter variant.
Terminal connections
Figure 15 Connections overview
123
4
5
123
4
5
AB AB
–+–+
123
4
5
6
7
8
Power Ammeter
SENSE
GUARD
RTD 1
RTD 2
SHIELD
RTD 3
REF
SOL_GND
12345678
12345678
12345678
DRIVE +
DRIVE –
RTD 1
RTD 2
SHIELD
RTD 3
DRIVE +
DRIVE –
RTD 1
RTD 2
SHIELD
RTD 3
SENSE +
SENSE –
DRIVE +
DRIVE –
RTD 1
RTD 2
SHIELD
RTD 3
SENSE +
SENSE –
Communication module connections
Sensor module connections
HART modules
HART modules
2-electrode conductivity modules
4-electrode conductivity modules
Toroidal conductivity modules
pH/ORP/plon modules