…Functions
Real Time Alarms 2 Independent real-time alarms can be configured to be activated on particular days and
times for a set duration.
Real Time Alarm 1
(2)
Sets the days the alarm is activated, the alarm duration, alarm display enable in the
diagnostics window and enables a (status bar) tag to be created for the alarm.
Monday (to Sunday)
Month enable
When enabled (On), activates the alarm on the 1
st
day of each month.
Every hour
When enabled (On), activates the alarm every hour.
On hour
Sets the hour the alarm is activated – not applicable if Every Hour is set to On.
On minute
Set the minutes past the hour the alarm is activated.
Duration
Set the duration the alarm is active.
Display enable
If disabled (Off), the alarm state does not appear in the operator level diagnostics window or
the alarm log.
Tag
A 16-character alphanumeric tag displayed as a diagnostic message that appears in the
Diagnostic Status Bar and in the Operator Level, Diagnostic View – see page 23.
Bank Control Bank control functionality enables a bank of output devices such as pumps, heaters or
fans to be switched On and Off under a duty / assist strategy.
If required, one of two different wear levelling schedules can be selected, Rotate or
FIFO (First In First Out).
Up to 6 stages may be configured for bank control, each of which can be assigned to a
relay or digital output. Each stage has an associated On trip value, Off trip value and
initial Output. All stages included in a wear levelling schedule must use the same
schedule type (Rotate or FIFO).
The example (overleaf) illustrates how the two modes operate to achieve wear levelling of 3
pumps in a duty / assist strategy.