II K 6-16
Operating Instructions
Stall protection
Commissioning step Comments
(17(5
to terminate the guided
commissioning procedure.
Yes
Stall Protection?
No
OUTPUT MENU A UT O OFF HA ND REM
LOC <RUN>
3.17 Stall Torque
100%
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
3.18 Stall Time
0.0s
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
5.15 Zero Speed Lev
50rpm
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
5.16 Speed Level 1
0rpm
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
5.17 Speed Level 2
0rpm
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Step Back
Exit Wizard?
Exit
OUTPUT MENU AUTO OFF HAND REM
LOC <RUN>
Stall torque
Stall time
Minimum speed
for zero speed detection.
Never set to 0 rpm with tacho or
encoder feedback.
Intermediate speed 1
for 'Speed 1 reached' signal
Intermediate speed 2
for 'Speed 2 reached' signal
End of guided commissioning
Don't forget to upload parameters into
the panel. Use function 'Copy to Panel'