EasyManua.ls Logo

ABB DCS 400 - Page 78

ABB DCS 400
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
II K 4-54
Overview of Software
ParNo. Parameter name and significance Min Max Default Unit (1)
custom.
setting
Grp 4 Field
4.01
Signal
Field Cur Ref
Field current reference value in amperes.
---A
4.02
Signal
Field Cur Act
Measured field current actual value in amperes.
---A
4.03
auto-
tuning
Field Cur KP
Proportional gain of the field current controller
(PI controller).
0.000 13.499 0.300 integer
4.04
auto-
tuning
Field Cur TI
Integration time constant of the field current
controller
(PI controller) in milliseconds.
0 5120 200 ms
Long Parameter Menu
4.05 Fld Ov Cur Trip
Field overcurrent tripping in % related to the field
current nominal value (1.03).
0 150 130 %
4.06 Field Low Trip
Field undercurrent tripping value in % related to the
field current nominal value (1.03).
Considerably lower values than the default setting
may be required for field weakening.
5 100 30 %
4.07
auto-
tuning
Field Cur 40%
Field current, at which 40% of field flux is reached.
Proportion of the nominal field current (1.03) in %.
0 100 29 %
4.08
auto-
tuning
Field Cur 70%
Field current, at which 70% of field flux is reached.
Proportion of the nominal field current (1.03) in %.
0 100 53 %
4.09
auto-
tuning
Field Cur 90%
Field current, at which 90% of field flux is reached.
Proportion of the nominal field current (1.03) in %.
0 100 79 %
4.10 Field Heat Ref
Current reference value for the field heating in %
related to the nominal field current value (1.03).
0 = without field heating
>0 = with field heating (heating current in %)
With this parameter, an anti-condensation heating
via the field winding can be implemented for the
motor.
The field heating starts 10 s after ON command
(without RUN command).
The field heating will switch on automatically
10 s after the drive is stopped (RUN=0) and the
actual speed is lower than Zero Speed Lev
(5.15).
When the drive starts again (
581
=1) the drive
will switch over to nominal field current.
0 30 0 %
4.11
auto-
tuning
EMF KP
Proportional gain of the EMF controller
(PI controller).
0.000 10.000 0.550 integer
4.12
auto-
tuning
EMF TI
Integration time constant of the EMF controller
(PI controller) in milliseconds.
0 10240 160 ms
(1) no changes possible if the drive is in ON-status

Table of Contents

Related product manuals