II K 4-59
Overview of Software
ParNo. Parameter name and significance Min Max Default Unit (1)
custom.
setting
Grp 5 Speed Controller (continued)
5.30 Act Filt 2 Time
Filter time constant 2 for smoothing speed deviation
at the input of the speed regulator.
0.00 10.00 0.00 s
5.31 Speed Lim Fwd
Speed reference limitation in forward direction. For
reason of safety, this settable limitation is
supplemented by an absolute, unchangeable
limitation to
Max Speed (1.06).
0 6500 6500 rpm x
5.32 Speed Lim Rev
Speed reference limitation in reverse direction. For
reason of safety, this settable limitation is
supplemented by an absolute, unchangeable
limitation to
Max Speed (1.06).
-6500 0 -6500 rpm x
5.33
Signal
Ramp In Act
Speed reference signal at Ramp Generator Input.
Shows the sum of Speed Ref + Aux Sp Ref.
Speed value greater than Max Speed (1.06) is
possible, a first limitation is done by ramp generator.
- - - rpm
5.34 Tacho Offset
Eliminate speed offset at motor shaft and panel
display.