II K 4-60
Overview of Software
ParNo. Parameter name and significance Min Max Default Unit
(1)
custom.
setting
Grp 6 Input / Output
6.01 AI1 Scale 100%
Scaling of analog input 1: input of a voltage value in
volts, which correspond to 100% reference.
2.50 11.00 10.00 V
6.02 AI1 Scale 0%
Scaling of analog input 1: input of a voltage value in
volts, which corresponds to 0% reference.
-1.00 1.00 0.00 V
6.03 AI2 Scale 100%
Scaling of the analog input 2: input of a voltage value
in volts, which corresponds to 100%.
2.50 11.00 10.00 V
6.04 AI2 Scale 0%
Scaling of the analog input 2: input of a voltage value,
which corresponds to 0%.
-1.00 1.00 0.00 V
Long Parameter Menu
6.05
Wizard
AO1 Assign
Desired assignment of analog output 1:
0 = Macro depend/ dependent on the selected macro
1 = Speed Act / actual speed value (5.05)
2 = Speed Ref / speed reference value (5.04)
3 = Arm Volt Act / armature voltage actual value (3.03)
4 = Arm Cur Ref / armature current refer. val. (3.01)
5 = Arm Cur Act / armature current actual value (3.02)
6 = Power Act / actual power (3.21)
7 = Torque Act / torque actual value (3.23)
8 = Fld Cur Act / field current actual value (4.02)
9 = Dataset 3.2
10 = Dataset 3.3
11 = AI1 Act / Analogue Input 1 actual value (6.26)
12 = AI2 Act / Analogue Input 2 actual value (6.27)
13 = Ramp In Act / Speed ref. at ramp gen. input (5.33)
0 13 0 Text
6.06
Wizard
AO1 Mode
Selection of the desired operating mode of analog
output 1:
0 = bipolar -11V…0V…+11V
1 = unipolar 0V…+11V
0 1 0 Text
6.07
Wizard
AO1 Scale 100%
Scaling of analog output 1:
Input of a voltage value in volts, which corresponds to
100% of the output signal.
0.00 11.00 10.00 V
6.08
Wizard
AO2 Assign
Desired assignment of the analog output 2:
Assignment identical with AO1 (6.05).
0 13 0 Text
6.09
Wizard
AO2 Mode
Selection of the desired operating mode of analog
output 2:
0 = bipolar -11V…0V…+11V
1 = unipolar 0V…+11V
0 1 0 Text
6.10
Wizard
AO2 Scale 100%
Scaling of analog output 2:
input of a voltage value in volts, which corresponds to
100% of the output signal.
0.00 11.00 10.00 V
(1) no chan