II K 4-72
Overview of Software
ParNo. Parameter name and significance Min Max Default Unit
(1)
custom.
setting
Grp 9 Macro Adaptation
Long Parameter Menu
9.01 MacParGrpAction
Before a new function can be assigned to a digital input
or control bit, the actual function has to be disabled. This
can be done in two ways. With par. 9.01 the function of all
assigned parameters 9.02...9.20 can be preset to disable.
The same can be achieved by setting the parameters
9.02...9.20 individually.
0=unchanged no parameters changes
1=Macro depend set parameters 9.02...9.20 to macro depend
2=Disable set parameters 9.02...9.20 to disable
Macro adaptation not possible for Macro 2, 3, 4
0 2 0 Text x
9.02 Jog 1
Jog function will be controlled from a binary signal which
is assigned in this parameter:
0=Macro depend
1=Disable
2=DI1
3=DI2
4=DI3
5=DI4
State of binary signal:
0=no Jog 1
Decelerate the motor by using Jog Decel Ramp
(5.20) till zero speed afterwards disable of
current controller .
1=Jog 1
enable current controller and accelerate the
motor by using Jog Acel Ramp (5.19) up to
Fixed Speed 1 (5.13)
Jog 1 function can also be controlled by bit 8 of Main
Control Word via serial communication - depending on
Cmd Location (2.02)
.
0 5 0 Text x
9.03 Jog 2
Jog function will be controlled from a binary signal which
is assigned in this parameter.
Assignment identical with 9.02
State of binary signal:
0=no Jog 2
Decelerate the motor by using Jog Decel Ramp
(5.20) till zero speed afterwards disable of
current controller .
1=Jog 2
enable current controller and accelerate the
motor by using Jog Acel Ramp (5.19) up to
Fixed Speed 2 (5.14)
Jog 2 unction can also be controlled by bit 8 of Main
Control Word via serial communication - depending on
Cmd Location (2.02)
.
0 5 0 Text x
9.04 COAST
Coast function will be controlled from a binary signal
which is assigned in this parameter.
Assignment identical with
9.02
Only effective if
Panel or PC tool
is not in LOCal Mode.
State of binary signal:
0=COAST
disable current controller, switch Main
Contactor Off, motor is coasting till zero
speed
1=no COAST
Closed-circuit principle, must be closed for
operation
The Coast function is also controlled by bit 1 of Main
Control Word via serial communication.
0 5 0 x
(1) no changes possible if the drive is in ON-status