Start-up   33
FEPL-02 configuration parameters – group A (group 1)
Note: The actual parameter group number depends on the drive 
type. Group A (group 1) corresponds to: 
•
parameter group 51 in ACS355, ACS380, ACSM1, ACS580, 
ACS850 and ACQ810
•
parameter group 51 in ACS880 if the adapter is installed as 
fieldbus adapter A or group 54 if the adapter is installed as 
fieldbus adapter B.
No. Name/Value Description Default
01 FBA type Read-only. Shows the fieldbus adapter 
type as detected by the drive. The value 
cannot be adjusted by the user. 
If the value is 0 = None, the communication 
between the drive and the module has not 
been established. 
136 = 
ETH Pwrlink
02 Profile Selects the communication profile for the
network connection.
0 = CiA 402
0 = CiA 402 CANopen device profile CiA 402
1 = ABB Drives 
profile
ABB Drives profile
2 = Transparent16 Transparent 16 profile
3 = Transparent32 Transparent 32 profile
03 Node ID Defines the node number of the device. 
Two units with the same address are not 
allowed on-line.
1
0…239 Node number