Start-up   41
Parameter setting examples – ACS355
Speed control using the CiA 402 velocity mode (vl)
This example shows how to configure a speed control application 
that uses the velocity mode (vl) of the CiA 402 profile.
When configuring the master, you need to map the following 
objects to the transmit and receive PDOs. For an example, see 
section Mapping objects required for controlling the drive on 
page 66.
The table below gives the recommended drive parameter settings. 
CANopen 
object
Output data CANopen 
object
Input data
0x6040 Control word 0x6041 Status word
0x6042 Target velocity 0x6044 Vl control effort
Drive parameter Setting for ACS355 
drives
Description
9802 COMM PROT SEL 4 = EXT FBA Enables communication between 
the drive and the fieldbus adapter 
module.
5101 FBA TYPE 136 = ETH Pwrlink
1)
Displays the type of the fieldbus 
adapter module.
5102 FB PAR 2 
(PROFILE)
0 (= CiA 402) Selects the CANopen device 
profile CiA 402.
5103 FB PAR 3 
(NODE ID)
3
2)
Defines the address of the 
device.
3018 COMM FAULT 
FUNC
1 = FAULT
2)
Enables fieldbus communication 
fault monitoring.
3019 COMM FAULT 
TIME
3.0 s
2)
Defines the fieldbus 
communication break supervision 
time.
5127 FBA PAR 
REFRESH
1 = REFRESH Validates the FEPL configuration 
parameter settings.