42 Start-up
The start sequence for the parameter example above is given
below.
Control word:
Reset the fieldbus communication fault (if active).
Enter 7Eh (126 decimal) SWITCH-ON DISABLED.
Enter 7Fh (127 decimal) OPERATION ENABLED.
1001 EXT1
COMMANDS
10 = COMM Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
1102 EXT1/EXT2 SEL 0 = EXT1 Enables external control location
1/2 selection through the fieldbus.
1103 REF1 SELECT 8 = COMM Selects the fieldbus reference 1
as the source of the speed
reference.
1601 RUN ENABLE 7 = COMM Selects the fieldbus interface as
the source for the inverted Run
enable signal (Run disable).
1604 FAULT RESET
SEL
8 = COMM Selects the fieldbus interface as
the source for the fault reset
signal.
1) Read-only or automatically detected/set
2) Example
Drive parameter Setting for ACS355
drives
Description