EasyManuals Logo

ABB FEPL-02 Ethernet POWERLINK User Manual

ABB FEPL-02 Ethernet POWERLINK
142 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
Start-up 57
The start sequence for the parameter example above is given
below.
Control word:
Reset the fieldbus communication fault (if active).
Enter 47Eh (1150 decimal) READY TO SWITCH ON.
Enter 47Fh (1151 decimal) OPERATING (Speed mode).
51.01 FBA type 136 = ETH Pwrlink
1)
Displays the type of the fieldbus
adapter module.
51.02 Profile 1 = ABB Drives profile Selects the ABB Drives profile.
51.03 Node ID 3
2)
Defines the address of the
device.
51.27 FBA par refresh 1 = Configure Validates the FEPL configuration
parameter settings.
20.01 Ext1 commands 12 = Fieldbus A Selects the fieldbus A interface
as the source of the start and
stop commands for external
control location 1.
20.02 Ext1 start trigger 1 = Level
2)
Defines the start signal for
external control location 1 as
level-triggered.
22.11 Speed ref1
selection
4 = FB A ref1 Selects the fieldbus A reference 1
as the source for speed
reference 1.
1) Read-only or automatically detected/set
2) Example
Drive parameter Setting for ACS880
drives
Description

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB FEPL-02 Ethernet POWERLINK and is the answer not in the manual?

ABB FEPL-02 Ethernet POWERLINK Specifications

General IconGeneral
BrandABB
ModelFEPL-02 Ethernet POWERLINK
CategoryAdapter
LanguageEnglish

Related product manuals