Electrical connections
42 FSM4000 D184B140U02
Retrofitting for model 10D1422: DN 3 ... DN 1000 (1/10 ... 40“); model 10DI1425 and 10DS3111A-E:
DN 500 ... DN 1000 (20 ... 40“)
S4 transmitter (wall mount housing)
G00241
L
M3 M1323151 52 41
N
8212S 2 161S342
3
7
6SE L N
7
6
381
24 V
12
1
1
1
1
2
3
4
5
6
7
1
8
9
10
Flowmeter sensor
Fig. 38: Flowmeter sensor standard DN 3 ... DN 1000 (1/10 ... 40"), transmitter field-mount housing
1 Functional ground (busbar)
2 Pulse output
1)
3 Contact input
1)
4 Contact output
1)
5 Current output
1)
6 Supply power
Low voltage: 100 ... 230 V AC, terminals L, N,
Frequency: 47 Hz f 53 Hz; 50 Hz supply power
Frequency: 56 Hz f 64 Hz; 60 Hz supply powe
r
7 Shielded signal cable: Use ABB order no. D173D025U01
or incorporate in existing wiring
8 Reference cable:
Only for connection to model 10D1422
Terminals: close 6,7 and the hook switch S903
9 Magnet coil supply:
Magnet coil supply via supply power
10 Connection board: D685A1020U03
1) See the section "Connection examples" in the operating instructions and/or on the data sheet
Comment:
We recommend that shielded output cables be used with the shields connected to the functional ground at one end.