Electrical connections
D184B140U02 FSM4000 43
DN 1 ... DN 1000 (1/25 ... 40") with PROFIBUS PA / FOUNDATION Fieldbus
S4 transmitter (wall mount housing)
G00597
M1 N
2- 1+
LM3
321S2S 3 16
U-U+
1
41 42 97
PA+
FF+
98
PA-
FF-
2
3
1
3c
SEM1M3
SE 3 2 U- 3A 16U+ 1
SE
M1
M3
SE
3 2 1S 3A 162S 1
7
11
12
108
10 10 13 14
9
4
5
1
1
1
1
1
1
6 6
3a
3b
15
16
Flowmeter sensor
Fig. 39: Connection diagram: transmitter SF with PROFIBUS PA / FOUNDATION Fieldbus
1 Functional ground (busbar)
2 Contact output (see the section "Connection examples for
peripherals" in the operating instructions and/or on the data
sheet)
3 Digital communication
3a: PROFIBUS PA design according to IEC 61158-2 (Profile
3.0)
3a: U = 9 ... 32 V, I = 10 mA (normal operation)
3a: U = 9 ... 32 V, I = 13 mA (in the event of error/FDE)
3a: Terminals: 97/98, PA+/PA-
3a: (see the section "Connecting via M12 plug" in the operating
3a: instructions and/or on the data sheet)
3b: FOUNDATION Fieldbus design conforming to IEC 61158-2
3a: U = 9 ... 32 V, I = 10 mA (normal operation)
3a: U = 9 ... 32 V, I = 13 mA (in the event of error/FDE)
3a: Terminals: 97/98, FF+/FF-
3a: (see the section "Connecting via M12 plug" in the operating
3a: instructions and/or on the data sheet)
3c: Bus termination with installed bus termination
3a: components with hook switches closed
4 Magnet coil cable:
shielded 2 x 1 mm
2
CE Typ 227 TEC 74
ABB order no. D173D147U01, 10 m included in shipment,
standard
5 Supply power
Low voltage: 100 ... 230 V AC, terminals L, N,
Low voltage: 20.4 ...26.4 V AC;
Low voltage: 20.4 ... 31.2 V DC
Low voltage: Terminals 1+, 2-,
Frequency: 47 Hz f 53 Hz; 50 Hz supply power
Frequency: 56 Hz f 64 Hz; 60 Hz supply power
6 Shielded signal cable:
Power supply for flowmeter sensor with preamplifier
Terminals U+, U- instead of 2S and 1S in standard unit
7 Steel shielding
8 Aluminum foil
9 Yellow
10 Shield
11 Blue
12 Red
13 White
14 Shielded signal cable: ABB order no. D173D025U01,
10 m, included in shipment
15 Without preamplifier
16 With preamplifier (always with DN 1 ... DN 8 [1/25 ... 5/16"])
Comment:
We recommend that shielded output cables be used with the shields connected to the functional ground at one end.
Important
If the flowmeter sensor is equipped with a preamplifier for low conductivity or in nominal diameter DN 1 ... DN 8
(1/25 ... 5/16"), the shieldings of the signal wires must be connected to terminals U+ and U- on both the flowmeter
sensor and the transmitter.