Electrical connections
46 FSM4000 D184B140U02
Bus termination for S4 transmitter
To terminate the bus if the instrument is at the end of the bus cable, the termination components in the S4 transmitter can be used. To do so,
close both hook switches in the connection area of the transmitter.
Important
If the transmitter plug-in module is removed, bus termination is also canceled.
G00249
M3 M141 42 97 98
U+ 2S 1 1S U- 332 16
6
7
Connection board for field housing unit
Hook switches for
bus termination must be closed
Fig. 45
Connection via M12 plug (for PROFIBUS PA only)
As an option, the bus can also be connected via an M12 plug instead of the cable gland (see order information for device). The device can be
shipped completely prewired. For information about suitable connectors (type EPG300) and other accessories, refer to the data sheet
10/63.6.44 DE.
G00250
1
2
34
Pin assignment
(Front view showing pin insert and pins)
PIN 1 = PA+
PIN 2 = nc
PIN 3 = PA-
PIN 4 = shield
Fig. 46