Parameterization
78 FSM4000 D184B140U02
Submenu/parameter Value range Comment
Warning Mask This menu shows the screen for the warning register (TB
Index 96).
Bitstring 0 OFF
Operation is identical to Error screen. See Warning
Register 9.8.3 and interface description D184B093U31,
page 47.
020000100
Warning: 10
Reverse Q
Software Rev. Display only Displays the communication software version.
Communication: 1
Submenu
i
Important!
Once the self-test function is initiated, the transmitter no
longer operates in online mode, i.e., the outputs no longer
track the flowrate.
Function test
Memory Test Test the memory. Internal FRAM, ext. FRAM and calc.
Flash can be queried in order via ENTER function.
Pulse output Numerical entry
This menu does not appear for the PROFIBUS PA or
FOUNDATION fieldbus.
Test the pulse output. Enter a value directly in Hz.
0 Hz
Current output 0 - 20 mA, 4 - 20 mA
0 - 10 mA, 2 - 10 mA
This menu does not appear for the PROFIBUS PA or
FOUNDATION fieldbus.
Test the current output. Check the value displayed at the
connection terminals using a digital voltmeter or the
process instrumentation. Enter a value directly in mA.
No selection available if the HART device address is
anything other than 0.
4 mA
Contact input Off
On
This menu does not appear for the PROFIBUS PA or
FOUNDATION fieldbus.
Test the contact input. Before a signal is applied to the
contact input, the text "Off" is displayed in this menu.
Once a signal is applied, the text "On" is displayed (to
check via simulator, use the Totalizer Reset key).
Off
Contact output Off
On
Test the contact output. When you set the value to "On",
the contact output selected is displayed for the configured
contact logic under the item Switch Contacts - Contact
Output.
Off
Display Test the display. Every point in the dot matrix is activated
one after another. Once all points are activated, a missing
point is easily detected.
Test Mode Off
On
Only for checking the transmitter using Simulator
55XC4000.
Off