Parameterization
D184B140U02 FSM4000 79
Submenu/parameter Value range Comment
Simulation Mode Off
On
On/Off function for Simulation mode. Before operation
with flow, a flowrate can be simulated. The output values
correspond to the simulated flowrate entered. The
information ** Q Simulation** is displayed in the lower line
of the display. After completing the simulation, change the
parameter in the Simulation Mode menu to "Off".
Off
Simulation Value Numerical entry
-130 % - +130 %
Select the simulation value for the display and outputs.
Current and pulse output follow the flowrate value.
0.0 %
Submenu Menu available only if the required hardware is available.
Diagnostics
Diagnostics Menu is displayed only with "Manual" diagnostic interval.
Manual
Start? Yes, exit via C/CE
Manually start manual diagnostic. The value is displayed
after a delay of 30 s.
Yes → Enter
Submenu
Diag. Interval
Cycle Time
Manual; 10 s; 60 s;
10 min; 60 min; 6 h;
12 h; 24 h; 7 d
Select the time interval between the individual diagnostic
measurements. For the values for Coil Resistance, Coil
Temperature, Insulation Resistance, and Magnetic
Linearity, however, there are minimum measurement
intervals for technical reasons related to the
measurement:
• 60 seconds for Coil Resistance and Coil Temperature
• 5 minutes for Magnetic Linearity
• 10 minutes for measurement of Insulation Resistance
These times are not undershot independently of the
configured diagnostic cyclic.
Manual
Submenu
In this menu you can set minimum and maximum values
for each measurement value. Depending on the selected
configuration, you can select for no message, a warning,
or an error message to be displayed, if the value falls
below or exceeds this threshold.
Alarm Settings
Submenu Set the time-out limits and alarm behavior for values over
or under the coil AC voltage.
Alarm Coil Voltage
Min. value 0 ... 150 Lower range limit for alarm
1.0 V
Max. value 0 ... 150 Upper range limit for alarm
150 V
Message Off, warning, error Defines the alarm behavior
Off