ABB i-bus
®
KNX
Parameters
100 2CDC508198D0211 Rev. A | AC/S 1.x.1
Gate (GATE)
Disables or enables the transmission of values.
If the gate element is disabled, the output remains unchanged and there is no recalculation.
Inputs
No.
DPT
Abbr.
Name
Invertible
Visible
Description
1
Any
E
Input
No
Always
2
1 bit
I
Control input
Yes
Always
Disables/enables the output
Outputs
No.
DPT
Abbr.
Name
Invertible
Visible
Description
1
Any
A
Output
No
Always
Parameters
Name
Value
Visible
Description
Control input triggers
calculation
Yes
No
Always
Yes: The output sends a value every time a
value is received on the control input.
Function
Control input = 1 (true): The output sends every time an input value is received (enabled)
Control input = 0 (false): The output does not send (disabled)
Other
If the control input is not connected, the transmission of values through the gate element is enabled.