EasyManuals Logo

ABB i-bus KNX AC/S 1.x.1 Series User Manual

ABB i-bus KNX AC/S 1.x.1 Series
488 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #388 background imageLoading...
Page #388 background image
ABB i-bus
®
KNX
Parameters
388 2CDC508198D0211 Rev. A | AC/S 1.x.1
7.12.4 Group objects
Object function
Name (can be
changed
separately)
Data point type
(DPT)
Length
Flags
C
R
W
T
U
I
Input: Supply temperature
Chiller
9.001
2 bytes
x
x
x
Input: Return temperature Chiller 9.001 2 bytes x x x
Output: Supply setpoint temperature Chiller 9.001 2 bytes x x x
Input: Pump relay status Chiller 1.001 1 bit x x x
Input: Pump repair switch status Chiller 1.011 1 bit x x x
Input: Pump fault
Chiller
1.011
1 bit
x
x
x
Input: Pump operating status (Off/On)
Chiller
1.011
1 bit
x
x
x
In-/Output: Pump override disable/enable
Chiller
1.003
1 bit
x
x
x
x
In-/Output: Pump override value
Chiller
1.001
1 bit
x
x
x
x
Output: Chiller On/Off Chiller 1.001 1 bit x x x
Input: Chiller operating status Chiller 1.011 1 bit x x x
Input: Chiller fault status Chiller 1.011 1 bit x x x

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals