ABB i-bus
®
KNX
Parameters
60 2CDC508198D0211 Rev. A | AC/S 1.x.1
7.2.2.3 BACnet parameter page
This parameter page is only available on the AC/S 1.2.1 Application Controller BACnet.
BACnet server enable
Options:
No (checkbox cleared)
Yes (checkbox selected)
Use this parameter to enable/disable the device's BACnet function globally. If the BACnet server is
disabled, it is not possible to communicate with the device via BACnet.
BACnet device object instance number
Options:
0…194302
Definition of the BACnet device address.
Note
The BACnet device address must be unique in the BACnet network and is not allowed to be assigned
twice.
BACnet device object name
Definition of the BACnet name of the device. The device uses this name in the BACnet network.
BACnet protocol port
Options:
47808…47823, 49152…65535
Definition of the IP port the BACnet server uses. This port must be set to suit the BACnet network.