ABB i-bus
®
KNX
Parameters
376 2CDC508198D0211 Rev. A | AC/S 1.x.1
Chiller
Enable chiller based on ASM input socket
Options:
No (checkbox cleared)
Yes (checkbox selected)
If this function is activated, an additional ASM input object for switching off/on the chiller is activated; the
value of this object is then forwarded to a chiller via a group object that is then displayed.
If the Switch off if no room demand
function is also activated, there is the following relationship:
ASM input socket
Chiller On/Off
Result of the
Switch off if
no room demand
function
Result and output in the
Chiller On/Off
group object
Off
Switched
off
Off
On
Switched off
On
Off
Switched on
Off
On
Switched on
On
Show operating status
Options:
No (checkbox cleared)
Yes (checkbox selected)
If the chiller outputs its operating status (Off/On), this status can be received by a group object via this
function and output on the web user interface, in a BACnet object and on the ASM socket.
Show fault status
Options:
No (checkbox cleared)
Yes (checkbox selected)
If the chiller outputs its error status, this status can be received by a group object via this function and
output on the web user interface, in a BACnet object and on the ASM socket.
The ASM only displays this state, there are no switching actions based on the fault status.