7.11.5 BACnet objects
Type
Object name
Object type
Unit
COV send
condition
Input Cooling distribution circuit: Supply setpoint temperature External
specification
Analog value °C (62) -
Output Cooling distribution circuit: Return temperature Analog value °C (62) 1.0
Output Cooling distribution circuit: Supply temperature Analog value °C (62) 1.0
Output Cooling distribution circuit: Supply setpoint temperature status Analog value °C (62) 1.0
Output Cooling distribution circuit: Outside temperature Analog value °C (62) 1.0
Output
Cooling distribution circuit: Supply setpoint temperature override
status
Binary value
-
-
Output Cooling distribution circuit: Supply setpoint temperature External
specification
Analog value °C (62) 1.0
Output Cooling distribution circuit: Control On/Off Binary value - -
Output Cooling distribution circuit: Control On/Off override disable/enable Binary value - -
Output Cooling distribution circuit: Room control values Analog value % (98) 1.0
Output Cooling distribution circuit: Pump A override disable/enable Binary value - -
Output
Cooling distribution circuit: Pump A override value
Binary value
-
-
Output
Cooling distribution circuit: Pump A operating status (Off/On)
Binary value
-
-
Output
Cooling distribution circuit: Pump A relay status
Binary value
-
-
Output
Cooling distribution circuit: Pump A fault
Binary value
-
-
Output Cooling distribution circuit: Pump A repair switch status Binary value - -
Output Cooling distribution circuit: Pump B override disable/enable Binary value - -
Output Cooling distribution circuit: Pump B override value Binary value - -
Output Cooling distribution circuit: Pump B operating status (Off/On) Binary value - -
Output Cooling distribution circuit: Pump B relay status Binary value - -
Output
Cooling distribution circuit: Pump B fault
Binary value
-
-
Output
Cooling distribution circuit: Pump B repair switch status
Binary value
-
-
Output
Cooling distribution circuit: Valve control value
Analog value
% (98)
1.0
Output
Cooling distribution circuit: Valve override disable/enable
Binary value
-
-
Output Cooling distribution circuit: Valve override control value Analog value % (98) 1.0
Output Cooling distribution circuit: Status Valve purge Binary value - -