ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 63
7.2.2.5 Clock parameter page
Clock synchronization source
Options:
NTP
KNX
BACnet
NTP: The device clock is set using a time server in the IP network or the Internet. The device must be
able to communicate with the time server and access must not be blocked (e.g. by a firewall).
KNX: The device clock is set via the KNX bus. The KNX time server must be connected to the related
device group objects.
BACnet: The device clock is set via the BACnet bus. The device clock must be set via the BACnet
time synchronization function by the BACnet time server.
Selection of NTP option:
Dependent parameter(s):
NTP server
Information on the IP address or the NTP time server's domain.
Time zone
Selection of the time zone in which the device is located.