ABB i-bus
®
KNX
Parameters
150 2CDC508198D0211 Rev. A | AC/S 1.x.1
WebUI to KNX
A value entered on the web user interface is sent by the group object using this template. The value
displayed on the web user interface cannot be changed via KNX. This value is also output on the ASM
output socket for linking to other modules.
The settings for the ASM socket, web user interface, KNX and BACnet are set automatically as follows:
ASM socket:
Output
WebUI:
Display + Set
KNX:
Output to KNX
BACnet:
None
Main data point type
Data point type
Definition of the data point type that is transferred between the interfaces.
You will find further information on the data point types in chapter 4.7 Data point types
.
Use value after restart
Options:
Last value
Initial value
This parameter defines which value is output in the group object after starting the application controller
until a new value is entered on the web user interface.
Last value: The last value before device start is saved and reused. The value parameterized further
down in Initial value is used after the first download of the module to the application controller.
Initial value: The value described further down in Initial value is used.