ABB i-bus
®
KNX
Parameters
194 2CDC508198D0211 Rev. A | AC/S 1.x.1
Cooling ceiling
Options:
None
On/Off
0…100%
Selects the cooling ceiling.
• None: A cooling ceiling is not used.
• On/Off: The cooling ceiling has a valve with the two settings open/closed, e.g. a solenoid valve. KNX
DPT 1.001 is used.
• 0…100%: The cooling ceiling has a continuous valve, e.g. a thermal or motorized valve. KNX DPT
5.001 is used.
Selection of On/Off and 0…100% option:
Dependent parameter(s):
Cooling ceiling, dew point alarm sensor
Options:
No (checkbox cleared)
Yes (checkbox selected)
This parameter specifies whether the status of the dew point alarm sensor is displayed on the web
user interface and is to be output in the BACnet object and on the ASM output socket.
Split unit
Options:
No (checkbox cleared)
Yes (checkbox selected)
This parameter specifies whether the status of a split unit (the usual terms are for example: split unit, air
conditioner, AC) in the room is displayed on the web user interface and is to be output in the BACnet
object and on the ASM output socket.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals