ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 241
All room setpoint temperatures for the operating modes activated are displayed on the web user interface.
Change the related room setpoint temperatures using the and buttons or using the keyboard. All
users with the exception of the "Viewer" have the right to change these values.
The room setpoint temperatures can be set in the range from 0 °C – 50 °C. A validation process makes
sure only the following sequence can be set:
1. Cooling Building Protection
2. Cooling Economy
3. Cooling Standby
4. Cooling Comfort
5. Dead band
6. Heating Comfort
7. Heating Standby
8. Heating Economy
9. Heating Building Protection
Every room setpoint temperature must equal to or greater than the previous. Furthermore, the dead band
set must be respected.