ABB i-bus
®
KNX
Parameters
248 2CDC508198D0211 Rev. A | AC/S 1.x.1
Radiator exponent
Options:
None/Linear (1.0)
Floor heating (1.05)
Floor heating (1.10)
Flat radiators (1.20)
Flat radiators (1.25)
Radiator to DIN 4703 (1.30)
Flat radiators (1.33)
Convectors (1.35)
Convectors (1.40)
Convectors (1.45)
Convectors (1.50)
The radiator exponent is dependent on the type and design of the heating element
and is normally stated by the manufacturer. The radiator exponent describes the
relationship between the increasing supply temperature and the non-proportionally
increasing heat dissipation into the room.
This information is used to calculate the heating curve. The higher this value is, the
more curved the heating curve is.
Start supply temperature curve at outside temperature
Options:
-100…19…100 °C
The outside temperature at which heating is started is specified using this parameter.
This value is the start of the heating curve. The heating limit is dependent on the
insulation standards in the building and can be selected lower, the better the building
is insulated.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals