ABB i-bus
®
KNX
Parameters
256 2CDC508198D0211 Rev. A | AC/S 1.x.1
Enable heating distribution circuit control based on ASM input socket
Options:
No (checkbox cleared)
Yes (checkbox selected)
If this function is activated, an additional ASM input object for the control (Off/On) is activated; the
value of this object is forwarded to the heating distribution circuit controller via a group object that is
then displayed.
If the Switch off if no room demand
function is also activated, there is the following relationship:
ASM input socket Control On/Off
Heating/cooling distribution
circuit controller control
Result of the Switch off if
no room demand
function
Result and output in the
Control
On/Off
group object
Off
Switched off
Off
On
Switched off
On
Off
Switched
on
Off
On
Switched on
On