ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 341
Selection of ASM input socket or BACnet input object option:
Dependent parameter(s):
Supply setpoint temperature offset
Options:
0…100 °C
An offset can be entered to compensate for the energy losses in the pipes. This value is
always subtracted from the supply setpoint temperature and is limited by the Min. supply
temperature parameter.
Selection of WebUI Input or BACnet input object option:
Dependent parameter(s):
Initial values
Supply setpoint temperature
Options:
0…10…100 °C
This parameter defines the supply setpoint temperature that is output after downloading the
module. This value is output until a new value is entered on the web user interface or is
written to the BACnet object. This value is limited by the Min. supply temperature parameter.