ABB i-bus
®
KNX
Parameters
AC/S 1.x.1 | 2CDC508198D0211 Rev. A 345
Pump
Settings for the cooling distribution circuit's pump.
Double pump
Options:
No (checkbox cleared)
Yes (checkbox selected)
This parameter specifies whether a double pump or a single pump is used in the cooling distribution circuit.
The group objects, BACnet objects, ASM sockets and the depiction on the web user interface are adjusted
to suit the setting.
Override by WebUI
Options:
No (checkbox cleared)
Yes (checkbox selected)
If this function is activated, the pump can be overridden via the web user interface. For this purpose
additional group objects are displayed that must be connected to the cooling distribution circuit controller.
Pump display operating status
Options:
No (checkbox cleared)
Yes (checkbox selected)
If the pump outputs its operating status (Off/On), this status can be received by a group object via this
function and output on the web user interface, in a BACnet object and on the ASM socket.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals