ABB i-bus
®
KNX
Parameters
404 2CDC508198D0211 Rev. A | AC/S 1.x.1
Interfaces
Change over based on
Options:
Outside temperature
Supply temperature
This parameter specifies the basis for the changeover between the heating and cooling operating type.
Selection of Outside temperature option:
Dependent parameter(s)
Cooling if greater than
Options:
-10…24…100 °C
The cooling operating type is activated as soon as the outside temperature at the ASM exceeds the
value set here.
Heating if less than
Options:
-10…17…100 °C
The heating operating type is activated as soon as the outside temperature at the ASM drops below
the value set here.
Selection of Supply temperature option:
Dependent parameter(s)
Cooling if less than
Options:
-10…15…100 °C
The cooling operating type is activated as soon as the supply temperature at the ASM drops below
the value set here. This means that the chiller is activated and provides cooling medium.
Heating if greater than
Options:
-10…30…100 °C
The heating operating type is activated as soon as the supply temperature at the ASM exceeds the
value set here. This means that the chiller is not active.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB i-bus KNX AC/S 1.x.1 Series and is the answer not in the manual?

ABB i-bus KNX AC/S 1.x.1 Series Specifications

General IconGeneral
BrandABB
Modeli-bus KNX AC/S 1.x.1 Series
CategoryController
LanguageEnglish

Related product manuals