PCS100 AVC-20 User Manual 69
The module failed to start
because of an error with
one of the following: (1)
NVRAM (2) FPGA (Field
Programmable Gate Array)
(3) Configuration ID.
The fault may be caused by
one of the following: The
Inverter’s IGBT (Insulated
Gate Bipolar Transistor) is
faulty. The Inverter IGBT is
overloaded. The IGBT
driver’s PCB (Printed Circuit
Board) is faulty.
Power down and restart. If the
fault is not resolved contact
your ABB Service Agent to
have relevant module replaced.
A reset was attempted too
soon.
Wait for 15 min before
pressing Reset.
One of the following
scenarios has occurred:
- The control power supply
has failed, or
- The auxiliary module is
faulty.
Check the AC supply voltage is
correct.
If the warning is not resolved,
contact your ABB Service
Agent to have the auxiliary
module replaced.
Two of the IGBTs (Insulated
Gate Bipolar Transistor)
from the same bridge are
activated.
Note: Only one should
activate at any one time.
Replace the faulty module.
There is an SPI (Serial
Peripheral Interface Bus)
watchdog error.
Ensure all communication
cables are connected and not
damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
There is a generic FPGA
(Field-Programmable Gate
Array) fault.
Check all communication
cables.
The DC Bus has risen to an
unsustainable voltage
because of one of the
following scenarios:
- The utility supply voltage
is too high
- There is excessive load
regeneration
Check the utility supply
voltage
Review the load types.
The DC Bus voltage is high.
There may be an earth fault
in the supply or excessive
load regeneration.
Wait until the DC voltage has
returned to normal.
If the warning is not resolved,
contact your ABB Service
Agent.