70 PCS100 AVC-20 User Manual
No action required.
The PCS100 AVC-20 will
automatically recover when
the input power returns to
normal.
No action required.
The PCS100 AVC-20 will
automatically recover when
the input power returns to
normal.
Inverter module zero
sequence current is too
high.
Contact your ABB Service
Agent to have the fault
resolved.
Zero Seq Abs
Current High
The PCS100 Module’s
absolute zero sequence
currents are too high.
Contact your ABB Service
Agent to have the fault
resolved.
The inverter and/or rectifier
lost synchronization with
master.
Check all communication
cables.
The inverter and/or rectifier
cannot synchronize with the
master within the timeout
period.
Ensure all communication
cables are connected and not
damaged.
If damaged, contact your ABB
Service Agent to have the
cables replaced.
Sustainable internal
condition. Control Loop
processing result late.
Press Reset.
If the warning is not resolved,
power down and restart.
There was an internal error.
Press Reset.
If the fault is not resolved,
power down and restart.
DSP stack has reached 75%
threshold level.
Power down and restart.
Notify your ABB Service Agent.
The pre-charge or bypass
contactor has not opened
within the required time-
out period.
Replace the faulty module.
The pre-charge or bypass
contactor has not de-
activated (auxiliary contact
detection) within the
required time-out period.
Replace the faulty module.
Precharge relay &
softcharge resistor is
enabled for too long.
Replace the faulty module.
Errors indicated by the
softcharge manager.
Replace the faulty module.
The softcharge sequence
takes too long, causing
restart sequence.
Replace the faulty module.
DC Bus ripple voltage high.
Check all three phases are
present.