PCS100 AVC-20 User Manual 71
The phase lock loop is not
locked to the input voltage.
This usually occurs when
the supply to the Rectifier
is switched off.
Check the utility supply.
If the warning is not resolved,
contact your ABB service
agent to have the utility and
load voltage sense connection
checked.
Model control loop
parameters out of range.
Replace the faulty module.
Second contactor
activation before recharge
delay has timed out.
Contact your ABB Service
Agent to have the fault
resolved.
Softcharge error if the DCV
< 0.15 PU after 200 ms, bus
not charging.
Contact your ABB Service
Agent to have the fault
resolved.
Either the FPGA (Field-
Programmable Gate Array):
- has not been reset, or
- did not initialize.
Press Reset.
If the fault is not resolved,
power down and restart.
Errors indicated by bypass
manager.
Contact your ABB Service
Agent to have the fault
resolved.
Bypass SCRs enabled too
long before bypass
contactor, detected in
hardware and contactor
forced closed.
Replace the faulty module.
Bypass SCRs on too long
when contactor remains
open (in AUTO BYPASS
mode).
Replace the faulty module.
Bypass SCRs remain on too
long (not turned off) after
contactor opened from
STOP to RUN transition.
Replace the faulty module.
With bypass open the
current in inverter and
bypass CT are not the
same.
Contact your ABB Service
Agent to have the fault
resolved.
With bypass closed, the
inverter CT still carries
current.
Contact your ABB Service
Agent to have the fault
resolved.
Out of
Regulation
Warning
One of the inverter three
phase output RMS voltages
differs from their reference
values by more than 10%.
One of the inverter three
phase output RMS voltages
differs from their reference
values by more than 25%.
Check voltage sensing circuits
including master DB9 cables.
Replace Inverter module.