FEM630 | ELECTROMAGNETIC FLOWMETER | OI/FEM630-EN REV. A
34 Use to call up the edit mode.
35 Use / to set the desired current for Low Alarm.
36 Confirm the selection with .
37 Use to call up the edit mode.
38 Use / to set the desired current for High Alarm.
39 Confirm the selection with .
22 Use to call up the edit mode.
23 Use / to select the desired pulse width for the
pulse output..
24 Confirm the selection with .
25 Use to call up the edit mode.
26 Use / to set the desired damping.
27 Confirm the selection with .
28 Use to call up the edit mode.
29 Use / to select the desired operating modeOff,
Logic, Pulse, Frequency for the digital output.
30 Confirm the selection with .
31 Use to call up the edit mode.
32 Use / to select the desired alarm mode.
33 Confirm the selection with .
Easy Setup
Pulse Width
30.00 ms
Next Edit
Easy Setup
Dig.Out 41/42 Mode
Pulse
Next Edit
Easy Setup
Curr.Out at Alarm
High Alarm
Next Edit
Easy Setup
Damping
25.000 ugal/s
Next Edit
Easy Setup
Low Alarm
3.500 mA
Next Edit
Easy Setup
High Alarm
21.800 mA
Next Edit
...7 Commissioning
Easy Setup