FEM630 | ELECTROMAGNETIC FLOWMETER | OI/FEM630-EN REV. A
Diagnostics / ...Diagnosis Control / ...Diagnosis Conductiv*
Conductivity On/Off
Activate the conductivity diagnostic function.
Default setting: Off
Note
For additional information, see Extended diagnostic functions
Adj. Cond. Value
Conductivity must be set in accordance with the conditions on-site.
Measure the conductivity using a conductivity meter on-site and enter the measured value here.
Cond. Iout Min Value
Cond. Iout Max Value
Cond.Min Alarm Value Set the alarm for minimum and maximum conductivity. In the case of down-scale, an alarm is triggered.
Cond.Max Alarm Value
Diagnostics / ...Diagnosis Control / ...Diagnosis SIL**
SIL On/Off
For information purposes only.
SIL devices are delivered ex works as SIL devices. There is no special SIL mode to activate
8 ...Operation
...Parameter descriptions
* The menu is only available if the Expert Diagnosis function is activated. See also the ‘Device Setup\...Transmitter\...Feature Settings’ menu.
** Menu only available if SIL diagnostic function is activated. See also the ‘Device Setup\...Transmitter\...Feature Settings’ menu.