7 - Operation
10. Voltage absence check on DC side
Access to the wiring box
02
by opening the front wiring box cover
07
.
Visually inspect the components to identify the presence of any
overheating, signs of electric arcs, failure of the insulating devices.
Check the all the LEDs installed on the positive string fuses plate
19
are OFF.
11. Check the absence of voltage on the DC terminal block using
the VAT
Check the absence of voltage on the DC terminal block measuring
between “Positive-ground”.
R S T N
19
CH1
CH3
CH5
CH2
PE
CH4
CH6
R S T N
19
CH1 CH2
CH3 CH4
CH5 CH6