EasyManuals Logo

ABB PVS-100 User Manual

ABB PVS-100
171 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
- 36 -
000829AG
2 - Characteristics
Topographic diagram of the equipment
The diagram summarises the internal structure of the inverter.
The internal circuitry is with double stage conversion and therefore con-
sists of:
- DC/DC input converter (booster)
- DC-AC output inverter
The DC-DC converter and the DC-AC inverter both work at a high
switching frequency and are therefore small and relatively light related
to output power.
The input converter is dedicated to multiple PV arrays with a maximum
power point tracking (MPPT) function in order to maximize the exporta-
tion of energy from the photovoltaic generator.
This inverter version is of the type without transformer, that is without gal-
vanic insulation between the input and the output. This allows ultimately
an increase in conversion efciency. The inverter is already equipped
with all the protections necessary for safe operation and compliance with
the norms, even without the insulating transformer.
The operation and the protection management of the inverter is control-
led by two independent DSPs (Digital Signal Processors) and a central
microprocessor.
A dedicate microprocessor is used for user communication interfaces.
The connection to the distribution grid is thus kept under control by two
independent DSPs, in full compliance with the electric eld norms both
for power supply to the systems as well as security.
The operating system carries out the task of communicating with its com-
ponents in order to carry out data analysis.
In doing all this, we guarantee optimal operation of the whole assembly
and a high performance in all irradiation conditions and always ensuring
full compliance with the relevant directives, standards and regulations.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB PVS-100 and is the answer not in the manual?

ABB PVS-100 Specifications

General IconGeneral
Rated AC power output100 kW
AC Voltage400 V
TopologyTransformerless
Cooling MethodForced Air
Operating temperature range-25°C to +60°C (derating above 45°C)
CoolingForced air
Frequency50/60 Hz