28 Hardware description
Testing (inverters only)
P945 Full power
burn-in
factory test
Inverter is operated with nominal power.
P954 Grid
protection
factory tests
(OV, UV, OF,
UF)
Grid protection factory tests (OV, UV, OF, UF)
P957 Extended
grid
protection
factory tests
(OV, UV, OF,
UF,
regulations)
Extended grid protection factory tests (OV, UV, OF, UF, regulations)
P958 Harmonics
factory test
Harmonics factory test
P959 Efficiency
factory tests
Efficiency factory tests
P960 Custom
factory tests
Custom factory tests
Specialities
P902 Customized Inverter is customized.
N840 Limited
output power
Inverter output power and/or current is limited (in practice output current) to a
pre-defined value based on utility and customer requirements. Additional
sticker is attached next to inverter type label that shows the actual limitation
value.
E203 EMC
compatibility
according to
old generic
IEC
standards
and FCC
standards
As standard, the inverter fulfills the new EMC limits set by IEC/EN 61000-6-2
and EN 55011. EN 55011 includes limits also on PV side emissions, the old
EMC standard does not include this. With +E203, the inverter complies with
old EMC standard IEC/EN 61000-6-4 and also FCC CFR 47, Part 15, Subpart
B, Class A (radiated only).
P956 40 °C ratings
(maximum
active current
limited
always to
1866 A)
Inverter current is limited to 1866 A and nominal values are referenced in this
point. This is a variant used in some markets.
Code Name Description