Finalizing the installation 43
Finalizing the installation
Contents of this chapter
This chapter tells you how to finalize and check the installation of the megawatt station.
Obey all local regulations.
WARNING! Only an authorized electrician is permitted to install the cabling to the
MWS. Obey the Safety instructions on page 9, and the local safety regulations. If
you ignore them, physical injury or death, or damage to the equipment may occur.
WARNING! Do not do electrical installation work during a thunderstorm.
Finalizing the installation of the megawatt station
• Clean the station of all dirt.
• Repair any damage on the paint surface.
Refer to To repair the painted surfaces on
page 58.
• Install the external hood for the fan. Refer
to Mechanical installation on page 33.
• Install the air inlet rain protection for the
transformer compartment.
Seal the cable entries, cover the cable entries with sand and sprinkle a handful of cement
over the sand. The cement hardens in a few days and it forms a barrier against small
animals and plant growth.