46 Start-up and operation
Prerequisites for the start-up
1. Remove the transportation canvas. Use the protection plates if there is a thunderstorm
warning.
2. Remove the sling of the medium-voltage switchgear.
3. Remove silica gel bags from the transformer compartment and auxiliary compartment.
Remove silica gel bags also from the inverters. Refer to the illustration for the
locations of the silica gel bags.
4. When you close the doors, make sure that the sealing gaskets are not caught in the
doors. If this occurs, use a screwdriver to carefully free the gasket. Do not cause
damage to the paint surface.
5. Refer to Tightening torques on page 52 for information on the torques for each item of
the container.